Time sync solutions for when you need to be certain
10 Year Warranty

 

GPS Clock - TCG 01-E

The TCG 01-E is a highly accurate, full featured GPS clock for use in electricity Distribution/Transmission and generation protection and control systems.

The clock synchronizes multiple IEDs (Intelligent Electronic Devices) within a network, including protection relays and remote telemetry units, and provides time-stamps to all electronic data being generated by the IEDs.

The TCG 01-E supports IEEE 1588 v2 (PTP) and IEC 61850.

GPS Clock_TCG 01-E
..view more images..      
Key Features
Inputs/Outputs
Specifications
Accessories
Resources
Able to act as an IEEE 1588 v2 (PTP) Grand Master, Master, Ordinary Clock or Slave Clock
Remote configuration via Ethernet
Ruggedized
Independently isolated outputs
Isolated power supplies
High output power line drivers
High noise immunity due to balanced pair distribution
UTC and LST with user defined DST options
Master/Slave function

 

PTP (IEEE 1588 v2)
DC IRIG-B (Unmodulated, DCLS)
AM IRIG-B (Modulated)
Serial Strings
User defined pulses  
DCF77
NTP/ SNTP (IEC 61850)  
TTL, RS232, RS422/ RS485, HV MOSFET, fiber
Event Recording

 

Datasheet_GPS Clock_TCG 01-E Click here for a PDF version of the specifications (325 KB).
Physical
Design: 19” rack mount 1U high
Measurements: (W) 160mm x (D) 155mm x (H) 40mm
Weight: 0.8Kg
Display: 2-line x 16 character FSTN backlit display
Inputs & Outputs
Two independent programmable outputs: TTL 0-5V, 150mA (BNC or 2-pin), or
RS422 +/- 5V, 50 loads (2-pin), or
HV switch MOSFET 300V 1A (2-pin), or
Fiber TX (62.5/125um, λ 820 nm), compatible with multi-mode fiber over ST Fiber connectors
RS232 serial port, DCE wired, Signals are +/- 10V, 15mA Serial time messages can be configured to be output at 1200, 2400, 4800, 9600, 19200 and 38400 baud.
Programmable pulse or IRIG-B available on pin 1
AM IRIG-B (B12x) (8Vpp, 120 ohm)  
2 x inputs
Input rating: 5 V, 7 mA (10 V, 20 mA also accepted)
External IRIG-B synchronization
Event time-tagging
2 x inputs
Contact rating: 200 V, 150 mA DC or 150 V, 100 mA AC
Antenna fail alarm
Sync relay
Network Time Server option

Network Time Server NTP/SNTP. Supports DHCP or fixed IP address

This UTP network interface option allows TCG 01-E to function as a Stratum 1 Time Server, simultaneously with all TCG 01-E i/o functions.

PTP v2 support Option
As per Network Time Server above plus:
  - PTP (IEEE1588) v2 operation
  GrandMaster (GPS) or ordinary clock functions (determined via BMC algorithm)
  - Profile selection: Default or Power
  - 1-step tx, 1-step/ 2-step rx
  - Layer 2 or Layer 3 mapping
  - Peer to Peer and End to End delay support
  - Multicast operation
Typical ordinary clock PPS accuracy (single sub- net) <250ns
Isolation
Outputs to base unit: 2.5kV
Power supply to I/O: 3.5kV
Between I/O: 5kV
Programmability
Customization is achieved using the Tekron Configuration Tool, which is accessed via Ethernet, allowing remote configuration.
Timing & Synchronization:

Worldwide daylight savings and local time configuration using either rule based or fixed date methods.

Options that allow equipment checks prior to full installation and adjustable hold-over times to increase reliability in the case of poor GPS coverage.

Adjustments to compensate for installation parameters such as delay of GPS signal through antenna cable.

Programmable Outputs:

IRIG-B (B00x / B22x) time code with selectable IEEE1344 and AFNOR S87-500 extensions

DCF77 time code

User defined pulse sequences: − Repetition rates from 20ms to 24 hours
− Offsets and durations from 10ms to 24 hours
− Resolution is 10ms, timing accuracy is 100ns

Serial Strings: NMEA-0183 ZDA
NMEA-0183 RMC
IRIG J-17
Tekron A—G: Seven protocols designed for plug and play compatibility with a wide range of equipment.
Pulse/Code Accuracy
TTL, RS422/ RS485, HV MOSFET, fiber: Code/pulse leading edges accurate to within 100ns of UTC under normal operation.
RS232 Port: Accurate to within 1.5us of UTC.
Antenna
Snow resistant, cone shaped antenna designed to fit over top of pipe like a capping.
Mounting: Internal diameter of 43.3mm fits a pipe with external diameter of between 40mm and 42mm. Fixed with m8 hex socket screws (supplied).
Measurement: 98mm tall, 90mm diameter.
Weight: 200g.
Gain: 35dB.
Bandwidth: 1575.42Mhz ± 1.023MHz.
Attenuation: 60dB (typical) at 1525/1625 MHz.
Environmental & Electrical
Power Drain: 6w max.
Operating Temperature: -10°C to +65°C  
Humidity: To 95% non-condensing  
Lightning Protection Kit
The antenna lightning protection kit affords additional protection through the use of an impulse suppressor installed in the antenna lead-in coax cable. In the event of a lightning-derived high voltage surge occurring on the coaxial cable, the impulse suppressor activates, short-circuiting the cable directly to the protection ground.
Kit contents (all components required to install lightning protection are included): - Impulse Suppressor
- 2 x N-type Male Crimp Style Coaxial cable
- Connector set to match antenna cable
- Crimp Tool to match the above connectors RG59).
Antenna mount
An adjustable 500mm powdercoated steel mounting bracket.
Datasheet_GPS Clock_TCG 01-E Technical Specifications datasheet  [Download datasheet - 320 KB]
GPS clock case study -<br />
            Transpower Case Study - Transpower. In 2000 Transpower, the national electricity grid operator in New Zealand, began an upgrade of their protection systems, which included installing GPS clocks in all their substations. To meet the accuracy demands of new protection technology, as well as the unique requirement for balanced, isolated outputs, they chose Tekron GPS clocks.
[Download case study - 170 KB]
GPS Clock TCG 01-E resources

Configuration Software, Quick Start Guide & User Manual.

This section is restricted to Tekron customers only. Click here if you are a Tekron customer and have not been issued a username and password.